Landis+Gyr ZxQ Yüksek Gerilim
Sayaçları

Yüksek gerilim hatlarında kullanılmak için tasarlandı.

ZxQ sayaçları, hassas veri ölçümü ve ağ için kapsamlı veri akışı sağlarken yüksek gerilim uygulamaları baz alınarak üretildi. Olağanüstü düşük reaksiyon süresi, yüksek veri çözünürlüğü ve kanıtlanmış güvenliği ile ZxQ sayaçların kesinlikle yüksek gerilim hatlarına uygun üretilmiştir.

Up to 36 measurement channels simultaneously register energy and operation values; the subsequent calculation for accounting and load parameters can be extensively individually programmed. The extremely fast measuring dynamic also permits very quick load changes, which improves the transmission area in particular in the monitoring of performance agreements. Unwanted harmonic waves (THD) can be recognized, which then makes the communication and accounting of line leakage and transformer losses (loss metering) possible.

Logically optimised for high operational security

The ZXQ helps energy providers in several ways by guaranteeing high quality: countless parameters can be continually monitored and read out as instantaneous values. A supplementary event memory holds up to 256 entries. The ZXQ is made only from high-quality construction materials giving it long-term application stability, and each meter has undergone a thorough testing process before delivery.

Broad data coverage, quick communication

The memory allocation of the 8MB Flash Memory allows individual adjustments. Up to 24 energy tariffs and 8 maximum registers are supported and can also save previous values and load profiles. Interchangeable communications modules enable quick read-out over standard interfaces (RS-232, RS 485, GSM, TCP/IP) as well as the manufacturing industry’s DLMS protocol.

Future-oriented management of high amounts of energy

Even in the liberalised market, it still holds true: in grid metering, it’s precision that brings cost effectiveness. The ZXQ supports EVU, which means the future is already built in: all 36 measuring channels can draw on the generation of highly flexible and demand-oriented accounting possibilities. The measurement of harmonic waves and an integrated dip table makes it possible to monitor the level of network quality as established in the contract. Large customers in turn have the chance to contractually set limits to the swings in the supply quality and can monitor this without any additional devices.


Products Page


Functions
  • Class 0.2S meter with transformer connection
  •  Especially developed for grid applications
  • Much faster measuring than commercial and industrial meters
  • Single-phase power registration of any energy or quadrant
  • Integrates network quality module with 36 registers
  • Communication and accounting of line and transformers losses
  • Registration and display of instantaneous values
  • Excellent measurement ratios for low loads as well as under full load
  • Up to 36 measurement channels, 24 energy tariff registers and 8 maximum registers
  • Previous values and load profile recording
  • Tariff control with internal events signals
  • RS-485 interface for direct connection to additional meters (daisy chain)
  • Operational monitoring with event memory, up to 256 events
  • 4 or 8 output contacts
Variations
  • Rack mount or wall mount housing
  • Interchangeable communications modules (RS 232, 485, GSM)
  • Module for PQ analysis according to EN-50160 optional